61
agility
TM
Series Soft Start User Manual
MAN-AGY-001. Version 04. 21/09/2018
PNU Name
Description
Options
Words Type Units Detail
109 Operation 2 Detects if the Control Board has failed to
operate normally
Trip On: System Trip enabled.
Trip Off: System Trip disabled.
0=Trip Off,
1=Trip On.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 1
Default: 1
110 Rerate Key The Key issued by Fairford to re rate the
unit to a different current rating
Use this parameter to enter the key
manually.
4
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 255
Default: 0
114 Shear Amps The current in Amps that will cause a
"Shear Trip"
A trip will occur if the motor current is
greater than the "Shear Amps" for the
"Shear Time"
2
R/W
A Multiplier: 1
Divisor:1000
Offset: 0
Min: 1 x PNU18
Max: 5 x
PNU22
Default: 3.5 x
PNU18
116 Shear TIme The trip time for the Shearpin trip
A trip will occur if the motor current is
greater than the "Shear Amps" for the
"Shear Time"
1
R/W
s Multiplier: 1
Divisor:1
Offset: 0
Min: 1
Max: 10
Default: 1