PNU Name
Description
Options
Words Type Units Detail
217 Diagnostic 6 Used for diagnostic purposes only
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 65535
Default: 65535
218 Ovld Amps Determines the level in Amps at which the
overload will start.
Normally set to 115% of the set "Motor
Amps"
Reduce to speed up trip response
2
R/W
A Multiplier: 1
Divisor:1000
Offset: 0
Min: 1 x PNU18
Max: 1.25 x
PNU18
Default: 1.15 x
PNU18
220
Language Selects the display language for the keypad
Enter the required language from the
displayed list
1=English,
2=Deutsch,
3=Francais,
4=Italiano,
5=Portugues,
6=Espanol.
1
R/W
Multiplier: 1
Divisor:1
Offset: 0
Min: 1
Max: 10
Default: 1
221 Total Starts The total number of successful starts
2
R
Multiplier: 1
Divisor:1
Offset: 0
Min: 0
Max: 65535
Default: 0