54
Instruction manual version 1 for software version 4.04
INSTRUCTION MANUAL FOR DAAB EP104 CONTROL BOARD
Programmable output 3
No.
Name
Range
Factory Setting Ref. page
o300
Function of output 3
0 - 4
1
0
Disabled
1
Position indicator/Movement/Warning Signal as configured in o310 – o322
2
Presence detection/Direction sensing Signal as configured in o391
3
Lock
4
Alarm output Signal as configured in o330 – o339
o310
Open position
0 - 1
1
0
Disabled
1
Constant signal
o311
Mid position
0 - 1
0
0
Disabled
1
Constant signal
o312
Closed position
0 - 1
0
0
Disabled
1
Constant signal
o313
Movement
0 - 3
0
0
Disabled
1
Constant signal in the opening movement
2
Constant signal in the closing movement
3
Constant signal in the opening and closing movement
o314
Delayed switch-off Switch off after the specified
time For example to switch off lighting a specified
time after closing
0.00-9.59min
0.00
o320
Warning time before start
0.00-9.59min
0.00
o321
Warning function in combination with o320
1 - 3
1
1
Constant signal before timed opening and automatic closing
2
Constant signal before close signal, timed opening and automatic closing
3
Constant signal before all signals
o322
Function during warning time
1 - 2
1
1
Output signal deactivated during warning
2
Signal as configured in o310-o313
o330
Alarm if there is an error as configured in
o331-o339. The alarm is activated for at least the
time set in this channel.
0.00-9.59min
0.00
o331
Alarm for faulty safety edge. Time as in o330.
0 - 1
0
0
Disabled
1
Constant signal
o332
Alarm for error message in display
0 - 1
0
0
Disabled
1
Constant signal