62
WT.050.810.040.DE.IM.0519
Retrofit kits, spares and accessories
DEPOLOX
®
5 E flow cell
6.
6.1.3
Replace standard cell body cover (optional)
The pressurized version can be retrofitted with the total chlorine mem
-
brane sensor TC3 CAN. Please note that the standard cell body cover
must be replaced by an optional cell body cover, part no. W3T417269.
Proceed as follows:
1
Unscrew the standard body cell cover.
2
Remove from the optional body cell cover (E) the union bush (A) with
dummy disc (B) and O-ring (C). Keep the parts for subsequent use
(equipped without membrane sensor for total chlorine).
3
Screw the optional body cell cover (E) into the lid of the cell body
(pressurized version).
4
First install the gasket W3T164773 and than the clamping ring
W3T171789 in the corresponding opening on the cell body cover (D)
5
Install the sensor measuring module DFMe for total chlorine TC3
CAN, see chapter 6.1.2 “Retrofitting sensor measuring modules, total
chlorine membrane sensor TC3 CAN and module SiDiSens conduc
Image 7 Cell body cover W3T417351
A Union bush
B Dummy disc
C O-ring
D Opening for cell body cover
E Cell body cover W3T417351
6.2
Spare parts
Please note
For reasons of safety, only use original spare parts. Please contact our
customer service if you need any spare parts.
6.2.1
DEPOLOX
®
5 E flow cell (module type D01)
A
B
C
E
D
Part No.
Designation
W3T350215
DEPOLOX
®
5 E flow cell
(module type D01) non-pressurized
W3T350216
DEPOLOX
®
5 E flow cell
(module type D01) pressurized
Summary of Contents for WALLACE & TIERNAN DEPOLOX 5 E 700 P Series
Page 1: ...WALLACE TIERNAN DEPOLOX 5 E FLOW CELL INSTRUCTION MANUAL...
Page 56: ...56 WT 050 810 040 DE IM 0519 Maintenance DEPOLOX 5 E flow cell 5...
Page 72: ...72 WT 050 810 040 DE IM 0519 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 76: ...76 WT 050 810 040 DE IM 0519 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 80: ...80 WT 050 810 040 DE IM 0519 Index DEPOLOX 5 E flow cell 8...