DEPOLOX
®
5 E flow cell
Maintenance
5.
49
5. Maintenance
Warning!
Risk of injury or death!
External voltages can be connected even with the operating voltage
switched off.
5.1
Maintenance intervals
Please note
Liability for defects can only be accepted if maintenance work is per
-
formed as specified. Adhere to the applicable standards and national and
regional regulations.
Activity
Period/Interval
Chapter/
instructions
Check for leakage
daily
Chapter 5.3
Cleaning or replacing the fine filter (with membrane
sensors only)
As required
Chapter 5.8
Comparative measurement, calibrate if necessary
Acc. to standard
See instruction man
-
ual for electronics
module.
Replacing the electrolyte for the total chlorine
membrane sensor
Every six months
See instructions on
Sensors
Replacing the membrane cap for the total chlorine
membrane sensor
Annually
See instructions on
Sensors
Checking the electrode cleaning sand
Weekly
Chapter 5.4
Replacing the electrode cleaning sand
Every six months
Chapter 5.4
Check electrolyte level
Regularly
Chapter 5.5
Check diaphragms
Depending on sam
-
ple water quality
Chapter 5.6
Replacing diaphragms
As required (depend
-
ing on sample water
quality), but at least
once a year
Chapter 5.6
Replacing reference electrode
As required, but at
the latest after two
years’ operation
Chapter 5.7
Summary of Contents for WALLACE & TIERNAN DEPOLOX 5 E 700 P Series
Page 1: ...WALLACE TIERNAN DEPOLOX 5 E FLOW CELL INSTRUCTION MANUAL...
Page 56: ...56 WT 050 810 040 DE IM 0519 Maintenance DEPOLOX 5 E flow cell 5...
Page 72: ...72 WT 050 810 040 DE IM 0519 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 76: ...76 WT 050 810 040 DE IM 0519 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 80: ...80 WT 050 810 040 DE IM 0519 Index DEPOLOX 5 E flow cell 8...