6. Operation
DEPOLOX® 400 M
56
EN
6.3
“System“ menu
Access to the operating and configuration
level of the electronics module is possible via
the System menu. All setting parameters not
relating to measured values, for example,
Alarms, I/O inputs and outputs, interface para-
meters etc., are parametrized via this menu.
1 Call up the Home menu.
2 Tap the symbol.
3 Tap the desired menu.
6.3.1
“
Operation mode“ menu
Select in this menu the operation mode.
1 Call up the Home menu.
2 Tap
or
symbole
or tap the symbole and than
Operation mode menu.
3 To switch to “Manual mode,” press the
“Change” button. An additional prompt
appears, i.e. in order to change the opera-
tion mode, you need to confirm the
prompt with “Yes” or “No.”
4 In “Manual mode,” it is possible to switch
the dosing contact on and off manually
via the “ON/OFF” button.
5 In “Automatic mode” it is possible to
switch to the settings level by pressing
the
symbol.
6.3.2
“
Calibration“ menu
In this menu, the measurements are compa-
red in compliance with the prescribed mainte-
nance intervals using calibration solution or
buffer solution or via comparative measure-
ments (chapter 6.6). The date of the last cali-
bration and the calibration value entered are
displayed. Depending on the desired measu-
rement, the corresponding calibration menus
can be selected. The menu can be opened in
via the System menu or via the Measure-
ment menu field.
Symbol/Menu
Meaning
Home menu
Home screen
Operation
mode
“Operation mode“
menu
Calibration
“Calibration“ menu
Inputs/Out-
pus
Configuration of inputs
and outputs
) Alarm confi-
guration
Configuration alarms
Login
Login screen for entry
of the password or
unlock code
Settings
Settings menu
Information
Info display
NOTICE
This function is only available if the parame-
ter “Disinfection controller = On” is set in the
menu “Settings – Setup.”
NOTICE
In “Manual mode“, the dosing contact only
switches off if the dosing contact is switched
off manually.