3. Description
DEPOLOX® 400 M
22
EN
Relay outputs
Type
6x changeover contact with integrated
fuse, replaceable, type TR5 3,15 A T
High nominal breaking
5A 250V AC, 1250VA max. (resistive
load)
1A 250V AC, 250VA max. (cos
ɸ
= 0,4)
5A 30V DC, 150W max. (resistive load)
Switching voltage max.
250V AC / 125V DC
Switching current max.
5A AC / DC
UL/CSA-rating
5A, 125/250V AC (general use)
1/6HP 125, 250V AC
5A 30V DC (resistive)
30W max., 1A, 30V DC – 0.24A, 125V DC
(inductive)
B300
NOTICE
When connecting inductive or capacitive loads (e.g. pump with integrated switching power
supply), an additional power relay with suitable specification must be provided. Each relay
output has an integrated 3.15 A fuse as overcurrent protection.
Typical use of the relay: Enabling contact for external alarm or trigger a dosing devices or
dosing pumps in constant flow applications.
Analog outputs
4-way mA output module 0/4 to 20 mA;
Freely configurable signal assignment;
Load max. 500 ohm, accuracy < 0.5 % FS ;
Galv. isolated up to 50 V relative to earth
Interfaces
RS485 interface with Wallace & Tiernan protocol for connection to
OPC server, Process Monitoring System or control system for data
visualization;
Ethernet interface (HTTP protocol/Modbus TCP protocol);
USB interface for firmware update