DEPOLOX® 400 M
6. Operation
61
EN
Max. dosing time:
00:00 to 10:00 h
This parameter defines a monitoring
time which specifies the maximum time
the controllers may require before the
measured value reaches the setpoint
minus monitoring hysteresis. If one of
the controllers does not reach the set-
point within the defined maximum
dosing time, the corresponding control-
ler is switched off and a message is
displayed. When the setting is
“00:00:00,” this function is switched off.
Notice: It is not possible in manual mode!
Monitoring hysteresis:
2 to 50 %
This parameter defines a range around
the setpoint within which the setpoint is
recognized as reached when dosing
time monitoring is enabled.
Safety MAN. mode
User administration
(chapter 6.3.8)
Access control:
This parameter is used to switch the
user administration on and off.
•
deactivated = no user administra-
tion; all parameters can be changed
without entering a password
•
activated = user administration ena-
bled, password protection or Level
1, 2 and 3 can be configured
Level 3:
If access control is enabled, as least
Level 3 must be used or configured.
Level 3 comprises read and write access
to all setting parameters of the device.
Unlock pattern:
Menu for entry/definition of a Level 3
unlock pattern. The entry must be
repeated as confirmation.
Password:
Menu for entry/definition of a Level 3
password. The entry must be repeated
as confirmation.
Level 2:
If access control is enabled, Level 2 can
be enabled or disabled. Level 2 allows
access to setting parameters such as
limit values, setpoint, date, time and
calibration. If Level 2 is enabled, an
unlocking pattern and/or a password
must be defined.
Unlock pattern:
Menu for entry of a Level 2 unlock pat-
tern. The entry must be repeated as
confirmation.
Password:
Menu for entry of a Level 2 password.
The entry must be repeated as confir-
mation.
Level 1:
If access control is enabled, Level 1 can
be enabled or disabled. Level 1 allows
access to calibration. If Level 2 is not
enabled, access to limit values and set-
points is also possible on Level 1. If Level
1 is enabled, an unlocking pattern and/
or a password must be defined.
Unlock pattern:
Menu for entry/definition of a Level 1
unlock pattern. The entry must be
repeated as confirmation.
Password:
Menu for entry/definition of a Level 1
password. The entry must be repeated
as confirmation.
Connection - Network
IP Adress:
Enter a fixed IP address (contact net-
work administrator)
Subnet mask:
Enter the subnet mask (contact network
administrator)
Gateway:
Gateway settings
DHCP:
On/Off
In the setting “DHCP = On,” the network
configuration is automatically defined
by the DHCP server and cannot be confi-
gured manually. The network settings
are displayed.
In the setting “DHCP = Off,” the network
settings must be configured manually.
Status HTTP Modbus