6. Operation
DEPOLOX® 400 M
66
EN
Fig. 4
Section, circuit board
A USB socket
B
Update button
6.5.1 LED glow stick color signaling
The color of the LED glow stick switches bet-
ween white, yellow and red depending on the
operating state (chapterl 6.3.6).
LED white
•
All OK.
•
The device is working trouble-free.
•
No active errors or currently no message
in the message system.
LED yellow
•
Alarm that is configured as “unlatched”
has been activated. As soon as the cause
was rectified and the alarm is inactive, the
yellow color signal changes again.
•
Fault message became active (only with
enabled tank monitoring and if the Min
message from the Cl2 or pH tank is pre-
sent.)
LED red
•
Error message present.
•
Alarm that is configured with acknowled-
gment has been activated.
6.6
Calibration
When calibrating the measurements, variati-
ons in the calibration solutions, buffer soluti-
ons or comparative measurements are
adjusted. Calibration is performed for new
devices (first commissioning) and to recali-
brate existing measuring instruments in accor-
dance with maintenance regulations.
6.6.1 Calibration interval
The electronics module offers the option of
using automatic maintenance and calibration
intervals for disinfection, pH, ORP (Redox) and
fluoride measurement. In as-delivered status,
the maintenance and calibration intervals are
disabled. Activated calibration interval:
1 Call up the Home menu
2 Select the desired measurement (e.g.
Chlorine free). The “Measurement” menu
opens.
3 Tap the
Settings menu. The settings
menu for the selected measurement
opens.
4 The “Maintenance interval” menu opens.
A
B
ATTENTION
Damage to sensor!
Electrodes are highly sensitive! Do not soil
or damage! Comply with the safety data
sheets for the buffer solutions or calibration
solutions.
NOTICE
•
Calibration must be carried out on first
commissioning.
•
The calibration intervals are defined
depending on the area of application
and water quality.
•
Please observe the prescribed mainte-
nance intervals (chapter 7.1).
•
Always start with the pH 7 calibration!
•
Before calibration of the pH value with
calibration solution, the ball valves on
the sample water inlet and sample
water outlet must be closed and the
pressure released.
•
Open the ball valves again after calibrat-
ion.