Product-manual Model: 637+/D6R KD6R
07-02-09-01-E-V0402.doc
49
5.6
Fuses, contactors, filters
Compact units
637+/ KD6R 02
.S4
KD6R 04
.S4
KD6R 06
.S4
KD6R 10
.S4
KD6R 16
.S4
KD6R 22
.S4
KD6R 30
.S4
-3
-7
-3
-7
-3
-7
-3
-7
-7
-7
-7
Fuses, Contactors
4)
RCD-switch
not recommended. Required setpoint: 300 mA, no protection against life danger
mains input currents
[A]
3,5
5
7,5
12
19
26
30
mains protection
1)
model
T10A
T10A
T10A
T20A
T25A
(T32A) 35A (T32A) 35A
protector-switch
2)
model PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-16 PKZM0-25 PKZ2/ZM32 PKZ2/ZM32
mains fuse
2)
model
DIL 00M
DIL 00M
DIL 00M
DIL 00M
DIL 0M
DIL 0M
DIL 0M
Line filters
4)
generall
only for use in earth referenced supplies(TN). Current drain to PE !
single-phase
industrial env.
max. motor cable 50m
(EN55011 A)
model
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
not possible
residential env.
max. motor cable 20m
(EN55011 B)
model
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
not possible
3-phase
industrial env.
max. motor cable 50m
(EN55011 A)
model
LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 6
LNF B 3*480/033
+
ferrite core FR 6
residential env.
max motor cable 20m
(EN55011 B)
model
LNF B 3*480/008
+
ferrite core FR 3
LNF B 3*480/018
+
ferrite core FR 3
LNF B 3*480/033
+
ferrite core FR 3
3-phasen, max. 3 Geräte versorgt durch einen gemeinsamen Filter
industrial env.
max. motor cable 20m
(EN55011 A)
model
LNF B 3*480/018; LNF B *480/033 + ferrite core FR
other models upon request
(according to ref.measurements with 3 units, supplied by common line)
residential env.
max motor cable 20m
(EN55011 B)
3)
model
LNF B 3*480/018; LNF B 3*480/033 + ferrite core FR
other models upon request
(according to ref.measurements with 3 units, supplied by common line)
Plug-in modules
637+ / D6R 02
.S4
D6R 04
.S4
D6R 06
.S4
D6R 10
.S4
D6R 16
.S4
D6R 22
.S4
D6R 30
.S4
-3 -7 -3 -7 -3 -7 -3 -7 -3 -7 -3
-7
-3
-7
Fuses, contactors,
filters
4)
1)
generall
Orientation: Table for compact units and the addition of rated currents of used
units on the DC-Bus. Depending on the application, energy sharing effects by
DC-link may reduce the required supply current considerable.
fuses
Rule of the thumb: single-phase operation: 2...3 times of added rated currents
Rule of the thumb: 3-phase operation: 1,5...2 times of added rated currents
peak making currents
Depending on power-supply unit, limiting equipment is requiered (delay contactor)
filters
only for use in earth referenced supplies(TN). Current drain to PE !
filter models
Orientation: Table of compact units. Further models: see separate manual
1) recommended for UL-requirements: Bussmann Type FRS-R, 600V, use only UL-approved fuse-holders !
2) recommended, Klöckner Moeller for instance
3) Measurement of conducted emissions only
4) for applications with continuous load: see notes in chapter 5.7
Summary of Contents for 637+/D6R KD6R
Page 78: ...78 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Page 79: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 79 Certificates ...
Page 80: ...80 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Page 81: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 81 Certificates ...
Page 82: ...82 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Page 83: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 83 Certificates ...
Page 85: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 85 16 Notes ...