5 - 4
5
590SP Digital Product Manual
Chapter 5 Troubleshooting
Figure 5.5 - Alarm Messages
Figure 5.4 - HEALTHY Output Logic
HEALTH, ALARM MESSAGES AND THE TRIP RESET
The controller continuously monitors 17 alarms while the drive is running. These alarms are gated together to provide
an overall "controller healthy" logic variable. This variable corresponds to the ALARM STATUS software block
output HEALTHY (tag number 122).
The default shipped drive configuration of the 590SP Digital drive tags the HEALTHY logic parameter to digital O/P 2
(terminal B6).
If a fault occurs while the controller is running, HEALTHY switches FALSE and the drive immediately inhibits the
thyristor firing circuit. The drive then deenergizes the main contactor and the MMI displays the last fault registered, or
the fault which interrupts controller operation. If TRIP RESET (parameter tag 305 set under the SETUP PARAM-
ETERS:: INHIBIT ALARMS menu) is TRUE, the HEALTHY output remains FALSE until the RUN input (terminal
C3) switches LOW, as shown in Figure 5.4. If a restart is attempted without first clearing the fault, HEALTHY will
again switch FALSE and the drive will not enable the thyristors and reenenergize the main contactor. If TRIP RESET
is FALSE, the drive cannot restart regardless of the state of the RUN input or whether or not the fault is cleared.
The tables in Figures 5.5 through 5.10 describe the different alarms the MMI displays when the drive trips out on a fault, the
fault's symptoms and recommended corrective action.
DISPLAY MESSAGE
MEANING
POSS
*** ALARM ***
5703 RCV ERROR
Drive not receiving communications
from external 5703 unit when
configured as a slave device
Cable from 570
into drive P3 po
5703 module n
communication
Drive incorrect
5703 peer-to-p
module failure
*** ALARM ***
AUTOTUNE ABORTED
Enable, or Start/Run commands
removed before AUTOTUNE
procedure completed
Wrong AUTOT
followed
AUTOTUNE inc
minutes drive w
AUTOTUNE mo
*** ALARM ***
AUTOTUNE ERROR
Motor rotation detected during
Autotune process (speed feedback
greater than 20%)
or
Field current detected during
Autotune. (Field current greater than
6%)
Residual motor
is disconnected
Series field win
motor
Permanent mag
Separately sup
Summary of Contents for 590SP
Page 2: ......
Page 16: ...1 4 590SP Digital Product Manual 1 Chapter 1 Introduction ...
Page 18: ...2 2 2 590SP Digital Product Manual Chapter 2 Identification ...
Page 31: ...Figure 3 3 Wiring Circuit Diagram for 590SP Digital Drive ...
Page 41: ...4 10 4 590SP Digital Product Manual Chapter 4 Start up and Adjustment DIGTIAL ...
Page 67: ...6 590SP Digital Product Manual Chapter 6 Service and Maintenance 6 6 ...
Page 89: ...B Appendix B Using the Man Machine Interface App B 4 590SP Digitial Product Manual ...
Page 125: ...Appendix C Setup Parameters 590 DRV Digital DC Drive Product Manual App C 36 C ...
Page 149: ...Appendix D I O Configuration System Menu App D 24 D 590SP Digital DC Drive Product Manual ...
Page 150: ...t t t t Figure D 20 590SP Digital Software Block Diagram ...
Page 160: ...590SP Digital Product Manual App E 10 E Appendix E MMI Parameter List ...
Page 168: ...Appendix G RS232 System Port P3 590SP Digital Product Manual App G 6 G ...
Page 194: ...Appendix H RS422 Communications Ports P1 P2 590SP Digital Product Manual App H 26 H ...
Page 220: ...App L 6 590SP Digital Product Manual L Appendix L 590SP DRV Option ...
Page 221: ...Figure L 5 Wiring Circuit Diagram for 590SP Digital DRV Drive ...
Page 259: ...590SP Digital Product Manual App M 38 Appendix M Special Blocks and Application Notes M ...