590SP Digital Product Manual
App. M - 12
Appendix M Special Blocks and Application Notes
M
OPEN-LOOP WINDER (CPW)
This configuration provides standard features used in center winder applications including: diameter calculation with
memory and preset, tension and taper, loss compensation, and over/under winding. It can control unwinds or rewinds
for single-spindle and turret winders. The configuration uses four function blocks in the SPECIAL BLOCKS menu;
DIAMETER CALC., TAPER CALC., TORQUE CALC., and SETPOINT SUM 2.
NOTE. This configuration does not support field weakening. A configuration containing field range
compensation is available. Call Eurotherm Drives Customer Support at (703) 471-4565 for detailed
instructions using this option.
A current programmed winder, CPW, provides constant tension center winder control by programming the motor ar-
mature current. The tension control is open-loop, that is, it does not use a dancer or loadcell feedback signal. The drive
maintains constant tension by controlling the motor torque. It keeps the torque proportional to the tension demand and
compensates for changing roll diameter with additional compensation for frictional losses.
NOTE. For accurate tension control, frictional losses must be small (and repeatable) compared to the
torque required to provide web tension.
Description
Figures M.11 and M.13 show typical winder and unwind applications. The diameter is reset before starting a new roll
by using terminal A2, EXTERNAL DIAMETER PRESET, for the diameter setting and C7, PRESET ENABLE, to
select the preset diameter. The drive starts when terminal C3, RUN, is set ON. Setting terminal C4 to ON selects ten-
sion mode. Once the line gets above a minimum speed the diameter calculator begins calculating the roll diameter.
NOTE. This configuration has disabled the JOG function, normally operated by terminal C4. Other
configurations can retain the JOG function.
In tension mode, an overspeed (underspeed for unwinds) is added to saturate the speed loop because the web holds the
winder at line speed. With the speed loop saturated, the drive is current limited by the torque demand. If the web
breaks, the winder increases to the speed loop limits, preventing a runaway.
Terminal C6, OVERWIND, changes the polarity of the torque demand and overspeed for overwinding or under-
winding.
Figure M.10 - Unwind Application
Summary of Contents for 590SP
Page 2: ......
Page 16: ...1 4 590SP Digital Product Manual 1 Chapter 1 Introduction ...
Page 18: ...2 2 2 590SP Digital Product Manual Chapter 2 Identification ...
Page 31: ...Figure 3 3 Wiring Circuit Diagram for 590SP Digital Drive ...
Page 41: ...4 10 4 590SP Digital Product Manual Chapter 4 Start up and Adjustment DIGTIAL ...
Page 67: ...6 590SP Digital Product Manual Chapter 6 Service and Maintenance 6 6 ...
Page 89: ...B Appendix B Using the Man Machine Interface App B 4 590SP Digitial Product Manual ...
Page 125: ...Appendix C Setup Parameters 590 DRV Digital DC Drive Product Manual App C 36 C ...
Page 149: ...Appendix D I O Configuration System Menu App D 24 D 590SP Digital DC Drive Product Manual ...
Page 150: ...t t t t Figure D 20 590SP Digital Software Block Diagram ...
Page 160: ...590SP Digital Product Manual App E 10 E Appendix E MMI Parameter List ...
Page 168: ...Appendix G RS232 System Port P3 590SP Digital Product Manual App G 6 G ...
Page 194: ...Appendix H RS422 Communications Ports P1 P2 590SP Digital Product Manual App H 26 H ...
Page 220: ...App L 6 590SP Digital Product Manual L Appendix L 590SP DRV Option ...
Page 221: ...Figure L 5 Wiring Circuit Diagram for 590SP Digital DRV Drive ...
Page 259: ...590SP Digital Product Manual App M 38 Appendix M Special Blocks and Application Notes M ...