Appendix A
Instruction Manual ATS 400 with SC-NG
Version 4.03
63
16
Appendix A SC-NG error numbers
The following are the error numbers of the safety circuit module. The error number is
displayed in
ETL DataView 3
in the field
state machine
.
Error number
Reason
Annotation
0x81
Unknown status in main
state machine
Problem in the firmware of the safety circuit
module.
0x82
Internal and external
status too uneven for a
long time
Problem in the firmware of the safety circuit
module.
0x83
Reset cause was watchdog Firmware of the safety circuit board was
restarted unintentionally.
0x84
AD conversion timeout
AD conversion took too long.
0x85
Invalid status in switch-
block of isFastSwitchOff ()
Problem in the firmware of the safety circuit
module.
0x86
Stack-Test
Problem in the firmware of the safety circuit
module.
0x87
ROM-Test
Problem in the firmware of the safety circuit
module.
0x88
RAM-Test
Problem in the firmware of the safety circuit
module.
0x8A
Current configuration too
often deviates from Init
configuration - MC1
The configuration has changed, e.g. In
operation, for example, the safety circuit plug
was removed or a cable break occurred.
0x8B
Current configuration too
often deviates from Init
configuration – MC2
The configuration has changed, e.g. In
operation, for example, the safety circuit plug
was removed or a cable break occurred.
0x8C
No configuration plug
(configuration 0 detected)
There is no configuration plug inserted.
0x90
Initialization: Configuration
1: no switch must be
pressed
When switching on or reset, a switch was
detected as being pressed. There is a cabling
error or the switch is defective.
0x91
Initialization: Configuration
2: Switches must be the
same (both open or both
closed)
When switching on or reset, a switch was
detected as being pressed. There is a cabling
error or the switch is defective.
0x92
Initialization: Configuration
3: Switches must be
pressed the same (similar
to above but 1C10)
When switching on or reset, a switch was
detected as being pressed. There is a cabling
error or the switch is defective.
0x93
Initialization: Configuration
5: "Start" must not be
active at startup
At the start, the safety circuit has already
been closed manually.
0x94
Initialization: Configuration
6: Both switches must be
pressed the same
Both OSSDs must have the same status. The
sending device may be defective.
0x95
Initialization: Configuration
7: Both switches must be
pressed the same or no
release_opener
The safety door switches are not actuated the
same or the door opener switch is not
plausible. There may be a cabling error.
0x96
Initialization: Configuration
8: Both switches must be
pressed the same
The safety door switches are not actuated the
same or the door opener switch is not
plausible. There may be a cabling error.