3. Usage
49
Press
or
to
adjust
the
blinking
value
Press "SET" to confirm the setting
.
If no operation for 6 seconds, it exits to main interface without saving the setting.
Group 0
List of parameters
0
1
2
Parameter No.
Meaning
Range
Default Value
0
0
60
0 (normal), 1(testing)
0 (invalid), 1(valid)
0 (invalid), 1 - 60 (checking
time, in seconds)
Indoor Control System Working Mode
External ON OFF Switch
Water Flow Switch
Heating Buffer Tank
3
0
0(no), 1(yes)
4
0
Cooling Buffer Tank
5
0
0 (hot Water), 1(heating)
Priority Switch Between Hot Water
and Heating Operation
0
0(off), 1(compressor System
1ON), 2(compressor System
2 ON)
Refrigerant collecting function
6
7
00
00 - 99 (in weeks)
Lock Function
0(no), 1(yes)
This function is designed for letting the installer test the output signals of the indoor control system
.
When
this
function
is
activated
,
indoor
control
system
will
activate the relay on the PCB when correspondent port on PCB is short-connected:
0
Parameter No.
Meaning
Range
Default Value
0
0 (normal), 1(testing)
Indoor Control System Working Mode
Port On PCB
Relay Output
Funtion
ES
FS
HS
CS
IRES
ES+FS
ES+HS
ES+CS
ES+IRES
CS+HS
W
W
EVC
EVW
SH
AS
HW
PUMPH
PUMPC
PO
RHS
YL
3-way valve (Cooling/Heating Port)
3-way valve (Hot Water Port)
Auxiliary Heater
Heating Back-up Heater
Domestic Hot Water Back-up Heater
Heating Distribution System Pump
Cooling Distribution System Pump
Unit Circulation Pump
Preserved-1
Preserved-2
【
System Setting
】
8
Available working modes
2(all
functions
)
0-DHW-1.Heating
-2
.
Cooling
+
Heating
+
DHW-3
.
Heating
Only-4
.
Heating
+
DHW
9
Stop/Speed down
Δ
T based on
set temperature in heating/cooling
2-10
2
℃
0a
Max Allowed Duration For Min
Compressor Speed
30 min
10-60(in minutes
)
Summary of Contents for AWH11-V5+
Page 2: ...2 ...
Page 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Page 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Page 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Page 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...