3. Usage
46
Heating Curve means let the system adjust the outlet water temperature based on the ambient temperature by continually
monitoring and adjusting in opposite direction with the current ambient temperature levels according to a pre-set curve,
to optimum comfort levels based on the changing heat demand,insulation levels,etc.
In a way, when it is colder (warmer) outside, house will need a higher (lower) temperature water to keep the same air
temperature in the house. Thus we can set a curve for the unit to follow, to let the unit adjust its set temperature for
heating operation
according
to
the
set
curve
and
actual
ambient
temperature
.
This function can be turned ON/OFF by adjusting the value of this parameter.
Heating Curve Function
D
1
1
0(invalid), 1(valid)
Parameter No.
Meaning
Range
Default Value
Unit
will
create
a
heating
curve
according
to
these
setting
.
Parameter D3, D5, D7, D9 and DB are used to set 5 different ambient temperatures
;
Parameter
D
4,
D
6,
D
8,
DA
and
DC
are
used
to
set
5
corresponding set water temperatures VS the set 5 ambient temperatures
.
Then
a
heating
curve
will
be
generated
automatically
.
Note: Value of parameter D3, D5, D7, D9 and DB should be in negative
direction
,
or
say
in
other
way
,
D
3>
D5
>
D7
>
D9
>
DB
,
otherwise
the
setting
of
the
value
may
not
saved
.
Parameter No.
Meaning
Range
Default Value
D3
D4
D5
D6
D7
D8
D9
DA
DB
DC
Ambient Temp. 1
Ambienttemp 1 Vs Water Temp. 1
Ambient Temp. 2
Ambienttemp 2 Vs Water Temp. 2
Ambient Temp. 3
Ambienttemp 3 Vs Water Temp. 3
Ambient Temp. 4
Ambienttemp 4 Vs Water Temp. 4
Ambient Temp. 5
Ambienttemp 5 Vs Water Temp. 5
-20 - 45
in
℃
20 - 65 (in
℃
-20 - 45
in
℃
20 - 65 (in
℃
-20 - 45 (
in
℃
)
20 - 65 (in
℃
-20 - 45 (
in
℃
)
20 - 65 (in
℃
-20 - 45 (
in
℃
)
20 - 65 (in
℃
(
)
)
(
)
)
)
)
)
12
25
7
28
2
31
-7
35
-20
42
0(invalid), 10 - 60(time
period for every adjustment,
in minutes)
Room Temp. Effect On Heating
Curve
D
2
0
Parameter No.
Meaning
Range
Default Value
If room temperature sensor is connected, "Set Room Temperature" in "Temperature Parameter" under "Basic Operation"
is set, and this "Room Temp. Effect On Heating Curve" is ON, unit will adjust the set water temperature (a set value or
calculated value via heating curve), according to the difference between actual room temperature and ideal room
temperature.
For example, if current water set temperature calculated according to the
heating
curve
is
35
℃
:
If actual room temperature is 27
℃
,
while
"
Set Room Temperature"
is
set
to
22
℃
,
then
the
unit
will
deduct
(27
℃
-22
℃
)=5
℃
from
water
set
temperature
,
which
means
unit
will
take
30
℃
as
the
final set temperature.
Summary of Contents for AWH11-V5+
Page 2: ...2 ...
Page 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Page 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Page 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Page 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...