3. Usage
33
Item
Sub-menu
Unit Statue
Operation
Level
Default factory
settings
Ambient temp. to start heating
20
Ambient temp. to start cooling
25°
°
Shifting priority
100°
Set room temperature
20°
Check in
ON/OFF, Set
in OFF
User
Temperature
Parameter
1.Code input: When unit is in "OFF" mode, press for 5 seconds, "----" will be shown. Press to swfit
between 4 positions, and press to adjust the value of the blinking value. Press "SET" to confirm the input
password. If the password is correct, "Advanced Setting" mode is activated.
2.Complete Advanced Setting menu is divided into 6 groups (Group 0~Group E). When Advanced Setting menu
is activated, press to switch between each group(Group 0, A, B, C, D,E) .
3.Press or to switch different parameters in the same group. Press "SET" to activate setting of current
parameter, with its value blinks, and adjust its value by or . Press "SET" to confirm the setting.
Item
Sub-menu
Unit Statue
Operation
Level
Default factory
settings
Advanced
Setting Group
0
Test working mode indoor controller
External ON/OFF switch
Water flow switch
Heating buffer tank
Cooling buffer tank
Priority switch between hot water
and heating operation
Refrigerant collecting function
Lock Function
Installer
OFF
0 (Normal
operation)
0 (Invalid)
60 sec
0 (No)
0 (No)
0 (hot water)
0 (OFF)
00 (OFF)
Advanced
Setting Group
A
Unit Circulation Pump Control
Type
Heating Circulation Pump Control
Type
Cooling Circulation Pump Control
Type
Heating Circulation Pump Start
Temperature
Heating Cirulation Pump Stop
Temperature
Cooling Circulation Pump Start
Temperature
Cooling Cirulation Pump Stop
Temperature
Installer
OFF
0 (unit controlled)
0 (unit controlled)
0 (unit controlled)
20°
18°
18°
20°
Page in
the menu
Page in
the menu
44
44
49~50
51
53
53
Available working modes
2(all
functions
)
Stop/Speed down
Δ
T based on
set temperature in heating/cooling
2
℃
30 min
Max Allowed Duration For Min
Compressor Speed
46~47
52
Summary of Contents for AWH11-V5+
Page 2: ...2 ...
Page 8: ...1 3 2 Monoblock unit 1 Before use 8 AW9 V5 AW11 V5 ...
Page 75: ...Cable connected to fan motor capacitor 4 4 Maintenance 5 75 ...
Page 80: ...5 Attached drawing Monoblock unit AW9 V5 80 157 95 60 317 156 1065 754 693 1053 343 354 50 ...
Page 85: ...5 Attached drawing Monoblock unit AWH9 11 V5 85 ...