4 Protection Functions and Specifications
4-34
L-PRO 4000 User Manual
D02706R02.30
Figure 4.18: 60 CT Supervision
81 Frequency
The relay has 4 frequency devices available. Each frequency element can be
set to operate either at a fixed level of under-frequency, a fixed level of over-
frequency, or at a rate of change level (df/dt). The df/dt function can be set to
operate for a positive rate of change or a negative rate of change. Each frequen-
cy element has a definite time delay setting to create a time delayed output. A
fixed level of positive sequence voltage of 0.25 pu provides an undervoltage
inhibit on each element
Figure 4.19: Frequency Fixed Level
Figure 4.20: Frequency Rate of Change
Table 4.17: 60 CT Supervision Settings
Main
Enable/Disable
Inps Pickup
0.25 to 5.00 A secondary (5A)
0.05 to 1.00 A secondary (1A)
Vnps Pickup
7.00 to 110.00 V secondary
Pickup Delay
0.03 to 99.99 seconds
Auxiliary
Enable/Disable
Inps Pickup
0.25 to 5.00 A secondary (5A)
0.05 to 1.00 A secondary (1A)
Vnps Pickup
7.00 to 110.00 V secondary
Pickup Delay
0.03 to 99.99 seconds
Table 4.18: 81 Over/Under Frequency Settings
Disabled/Fixed Level/Rate of Change
T
O
Frequency (Hz)
T
O
df/dt (Hz/s)
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......