7 Acceptance/Protection Function Test Guide
D02706R02.30
L-PRO 4000 User Manual
7-53
Figure 7.34: Test Connections for 4-Shot Recloser Test
ProLogic equations are used to activate and supervise the 79 test functions.
Normally each of these ProLogic equations would not be set to target, but for
this type of acceptance testing, it is convenient for seeing operations as they
happen.
Details of ProLogic Equations for this 79 Test Example
ProLogic 1: This equation activates the reclose sequence. It sets the breaker
status (closes Out 5) via ProLogic 3.
Figure 7.35: Simulating Main Breaker Close Command using Virtual Input in ProLogic
ProLogic 2: This equation is used to reset the Main Breaker Status via ProLog-
ic 3 (Opens Out 5).
125
Vdc
+
_
EI2
EI3
OUT 6
(52a)
OUT 7
(Trip)
212
213
102
103
104
105
214
215
Aux
Breaker
Status
Trip and
79
Initiate
EI1
OUT 5
(52a)
210
211
100
101
Main
Breaker
Status
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......