7 Acceptance/Protection Function Test Guide
D02706R02.30
L-PRO 4000 User Manual
7-5
Download
Acceptance
Test File
1. Browse to find the following Offliner Setting file
“LPROaccTestsetting60hz” in C:\Program Files\ERLPhase\LPRO Offlin-
er Settings\.
2. Double-click the
Setting
file to open. Enter the serial number of the relay
being tested or check
Ignore Serial Number
checkbox.
3. Select
File
on the menu bar, then select
Convert to Newer
under its sub-
menu, select
version 404
.
Figure 7.3: Identification Serial Number Screen
4. Save the file.
5. Connect to the relay in Service or Change mode via the relay front port (Port
150) using the Relay Control Panel.
6. From the Main Menu double click on
Configuration.
7. From the Configuration submenu select
Import
.
8. Browse to the converted acceptance test file and click on
Open.
9. Select the file under Saved Settings list and click on the
Load to IED
button
on the right.