Appendix A IED Specifications
Appendix A-2
L-PRO 4000 User Manual
D02706R02.30
Input & Output:
Analog Voltage Inputs
2 sets of 3-phase voltage inputs
(6 voltage channels total)
Nominal Voltage
Continuous rating over voltage
Maximum over-scale thermal rating
Burden
Vn = 69 Vrms
2x Vn = 138 Vrms
3x Vn = 207 Vrms for 10 seconds
<0.15 VA @ 69 Vrms
Analog Current Inputs
4 sets of 3-phase current inputs
(12 current channels)
Nominal Current
Full Scale/Continuous
Maximum full-scale rating
Thermal rating
Burden
In = 1 Arms or 5 Arms
3x In = 3 Arms or 15 Arms
40x In for 1 second symmetrical
400 Arms for 1 second
<0.25 VA @ 5 Arms
Amplitude measurement accuracy
+/-0.5% for 54 to 66 Hz
+/-0.5% for 44 to 56 Hz
Analog Sampling Rate
96 samples/cycle for recording
8 samples/cycle for protection
Records up to 25th harmonic
Burden
Burden resistance: > 10 k ohms
External Inputs
9 isolated inputs (3U chassis)
20 isolated inputs (4U chassis)
Optional 48, 110/125 or 220/250 Vdc
nominal, externally wetted
Isolation
2 KV optical isolation
Output Relays (contacts)
14 programmable outputs (3U chassis) and 1
relay inoperative contact (N.C.)
21 programmable outputs (4U chassis) and 1
relay inoperative contact (N.C.)
Externally wetted
Make: 30 A as per IEEE C37.90
Carry: 8 A
Break: 0.9 A at 125 Vdc resistive
0.35 A at 250 Vdc resistive
Virtual Inputs
30 Virtual Inputs
Interface & Communication:
Front Display
240 x128 pixels graphics LCD
Front Panel Indicators
16 LEDs: 11 programmable, 5 fixed
Fixed: Relay Functional, IRIG-B Func-
tional, Service Required, Test Mode,
Alarm Target (11 programmable)
Default assignments: Ground Distance,
Phase Distance, Phase Overcurrent,
Breaker Failure, Over/Under-Fre-
quency, Switch On To Fault, Communi-
cation Trip, Power Swing Trip, ProLogic
1 - 8, ProLogic 9 - 16, ProLogic 17 - 24
Front User Interface
USB port and 100BASE-T Ethernet port
Full Speed USB 2.0, RJ-45
Rear User Interface
LAN Port 1: 100BASE Copper or Optical
1300nm
LAN Port 2: 100BASE Copper or Optical
Two Serial RS-232 ports to 115 kbd modem
Copper: RJ-45, 100BASE-T
Optical: 100BASE-FX, Multimode ST
style connector
Com port can support external modem
Internal Modem
33.6 Kbps, V.32 bis
Optional internal modem
SCADA Interface
IEC61850 (Ethernet) or DNP3 (RS-232 or
Ethernet) or Modbus (RS-232)
Rear port
Time Sync
IRIG-B, BNC connector
B003,B004,B123 and B124 Time Codes
Modulated or unmodulated, auto-detect
L-PRO Model 4000 Specifications
Summary of Contents for L-PRO 4000
Page 1: ...L PRO 4000 Transmission Line Protection Relay User Manual Version 2 3 Rev 0...
Page 2: ......
Page 4: ......
Page 8: ......
Page 10: ......
Page 14: ......
Page 40: ......
Page 50: ......
Page 116: ......
Page 146: ......
Page 218: ......
Page 252: ...Appendix B IED Settings and Ranges Appendix B 34 L PRO 4000 User Manual D02706R02 30...
Page 260: ......
Page 270: ......
Page 302: ......
Page 308: ......
Page 310: ......
Page 312: ......