38
Entek IRD 6666 and 6667 Protection Monitors
Configuration
2.
Select the relay you want to set. For this example, you want to set relay 2, so select
RLY2MAP.
3.
To set the first source, select RLYSRC1. Note that this menu might contain additional
source options. The first source you need to set for relay 2 is the first alarm map
(ALM1MAP).
4.
Select RLY2 1 (relay 2, source 1) and set it to ALARM. Note that you choose ALARM
when your source is a combination of two alarms.
5.
Select SRC NUM and set it to 1 for ALM1MAP.
6.
Since you are combining the sources with an OR, select COMBINE and set it to OR.
You have now mapped the first alarm map (ALM1MAP) OR another source to relay 2.
You now need to set the second source (the second alarm map).
7.
Select EXIT.
8.
To set the second source, select RLYSRC2.
The second source for relay 2 is the second alarm map (ALM2MAP).
RLY3MAP
RLY4MAP
RLY5MAP
RLY6MAP
RLY7MAP
EXIT
RLY2MAP
SET
EXIT
RLYSRC1
SET
SRC NUM
1
COMBINE
OR
EXIT
SET
RLY2 1
ALARM
EXIT
RLYSRC2
SET
RLYSRC1