Configuration
Entek IRD 6666 and 6667 Protection Monitors
25
RISING submenu
For each channel you can choose to activate an alarm on a signal level rising or falling
through the alarm setpoint.
z
YES - The alarm is activated on a signal level rising through the alarm setpoint. The
Danger setpoint should be above the Alert setpoint.
z
NO - The alarm is activated on a signal level falling through the alarm setpoint. The
Danger setpoint should be below the Alert setpoint.
DELAYS submenu
The DELAYS submenu has the following options. These options apply to all channels of
the monitor.
Note: The GLOBAL alarm delays do not affect the System OK relay.
RISING 2
RISING 3
RISING 4
RISING 5
RISING 6
EXIT
RISING 1
SET
Factory menu
→
RELAYS
→
ATTRIBS
→
RISING
RISING 1
Choose the alarm activation for channel 1 (YES, NO).
RISING 2
Choose the alarm activation for channel 2.
RISING 3
Choose the alarm activation for channel 3.
RISING 4
Choose the alarm activation for channel 4.
RISING 5
Choose the alarm activation for channel 5.
RISING 6
Choose the alarm activation for channel 6.
EXIT
Return to the ATTRIBS submenu. The monitor remembers the current
values for menu options, but does not write them to memory until you exit
the Factory menu.
STARTUP
3.0
SECS
EXIT
SET
GLOBAL
1.0
SECS
Factory menu
→
RELAYS
→
DELAYS
GLOBAL
Choose the alarm delay that applies to all alarms (0.0–30.0 sec). The
alarm must persist for this length of time before the monitor
acknowledges the alarm and changes any relays.
STARTUP
Choose the length of time during which the monitor inhibits the Danger
alarm relays (0.0–30.0 sec). The start-up period begins when terminal 11
(START UP INHIBIT/MULTI) is connected to terminal 46 (DIGITAL
COMM).
EXIT
Return to the RELAYS submenu. The monitor remembers the current
values for menu options, but does not write them to memory until you exit
the Factory menu.