Configuration
Entek IRD 6666 and 6667 Protection Monitors
37
3.
Select ALM2 1 (alarm map 2, source 1) and set it to ALERT.
4.
Select SRC NUM and set it to 2 for channel 2.
5.
Since you are combining the sources with an AND, select COMBINE and set it to
AND.
You have now set the first half of the second equation:
relay 2 = channel 2 Alert AND source 2
You now need to set the second source.
6.
Select EXIT.
7.
To set the second source in ALM2MAP, select ALMSRC2.
The second source for ALM2MAP is a channel 1 Danger alarm.
8.
Select ALM2 2 (alarm map 2, source 2) and set it to DANGER.
9.
Select SRC NUM and set it to 1 for channel 1.
10. Since this is the last source in ALM2MAP, select COMBINE and set it to END.
You have now set ALM2MAP to channel 2 Alert alarm AND channel 1 Danger alarm.
You now need to set the relay map to map ALM1MAP OR ALM2MAP to relay 2.
11. Select EXIT three times to return to the RLY MAP option.
To set the relay map
1.
Select RLY MAP.
SRC NUM
2
COMBINE
AND
EXIT
SET
ALM2 1
ALERT
EXIT
ALMSRC2
SET
ALMSRC1
SRC NUM
1
COMBINE
END
EXIT
SET
ALM2 2
DANGER
ALM MAP
FAILSAFE
EXIT
RLY MAP
SET