Configuration
Entek IRD 6666 and 6667 Protection Monitors
33
5.
Select RLY2 1 (relay 2, source 1) and set it to ALERT.
6.
Select SRC NUM and set it to 3 for input channel 3.
7.
To combine the sources with an AND, select COMBINE and set it to AND.
You have now set the first half of your equation:
relay 2 = channel 3 Alert AND source 2
You now need to set the second source.
8.
Select EXIT.
9.
To set the second source, select RLYSRC2.
The second source you need to set for relay 2 is a Danger alarm for input channel 5.
10. Select RLY2 2 (relay 2, source 2) and set it to DANGER.
11. Select SRC NUM and set it to 5 for input channel 5.
12. Since this is the last source, select COMBINE and set it to END.
You have now set the second source for the equation:
relay 2 = channel 3 Alert AND channel 5 Danger
13. Select EXIT. You can set the combination of alarms for other relays by repeating these
steps.
SRC NUM
3
COMBINE
AND
EXIT
SET
RLY2 1
ALERT
EXIT
RLYSRC2
SET
RLYSRC1
SRC NUM
5
COMBINE
END
EXIT
SET
RLY2 2
DANGER