Proline Promag W 400 HART
Electrical connection
Hauser
45
Connecting the connecting cable to the transmitter
1.
2.
4.
3.
6 5 7 8 4 37 36
42 41
S1
E1
E2
S2
GND
E
S
TX 20
4 x
A0032102
18
Transmitter: main electronics module with terminals
1. Loosen the 4 fixing screws on the housing cover.
2. Open the housing cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules
5. Connect the cable in accordance with the terminal assignment → 41.
6. Firmly tighten the cable glands.
7.
L
WARNING
Housing degree of protection may be voided due to insufficient sealing of the
housing.
‣
Screw in the screw without using any lubricant.
Reverse the removal procedure to reassemble the transmitter.
7.2.2
Connecting the transmitter
L
WARNING
Housing degree of protection may be voided due to insufficient sealing of the housing.
‣
Screw in the screw without using any lubricant. The threads on the cover are coated
with a dry lubricant.
Tightening torques for plastic housing
Housing cover fixing screw
1.3 Nm
Cable entry
4.5 to 5 Nm
Ground terminal
2.5 Nm
For HART communication: when connecting the cable shielding to the ground
terminal, observe the grounding concept of the facility.