Commissioning
Proline Promag W 400 HART
98
Hauser
Parameter
Prerequisite
Description
User entry /
Selection
Factory setting
Assign pulse output
In the
Operating mode
parameter, the
Pulse
option is
selected.
Select process variable for
pulse output.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Off
Measuring mode output 1 to n
–
Select measuring mode for
output.
• Forward flow
• Forward/Reverse
flow
• Reverse flow
• Reverse flow
compensation
Forward flow
*
Visibility depends on order options or device settings
10.4.8 Configuring the low flow cut off
The
Low flow cut off
wizard systematically guides the user through all the parameters
that must be set to configure low flow cut off.
Navigation
"Setup" menu → Low flow cut off
‣
Low flow cut off
Assign process variable
On value low flow cutoff
Off value low flow cutoff
Pressure shock suppression
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign process variable
–
Select process variable for low
flow cut off.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
On value low flow cutoff
One of the following options is
selected in the
Assign process
variable
parameter (→ 98):
• Volume flow
• Mass flow
Enter on value for low flow cut
off.
Positive floating-
point number
Depends on country
and nominal
diameter