Electrical connection
Proline Promag W 400 HART
42
Hauser
2. If the measuring device is supplied without cable glands:
Provide suitable cable gland for corresponding connecting cable.
3. If the measuring device is supplied with cable glands:
Observe requirements for connecting cables → 38.
7.1.7
Preparing the connecting cable for the remote version
When terminating the connecting cable, pay attention to the following points:
1. In the case of the electrode cable:
Make sure that the ferrules do not touch the core shields on the sensor side.
Minimum distance = 1 mm (exception: green “GND” cable)
2. In the case of the coil current cable:
Insulate one core of the three-core cable at the level of the core reinforcement. You
only require two cores for the connection.
3. For cables with fine-wire cores (stranded cables):
Fit the cores with ferrules.
Transmitter
Electrode cable
Coil current cable
A
80 (3.15)
50 (1.97)
17 (0.67)
8 (0.31)
100 (3.94)*
B
GND
1
2
1
2
1
2
2
A0032093
15
Engineering unit mm (in)
A
90
*
(3.54)
70 (2.76)
50 (1.97)
10 (0.39)
8 (0.31)
B
1
A0032096
16
Engineering unit mm (in)
A = Termination of the cables
B = Termination of the fine-wire cores with ferrules
1 = Red ferrules, 1.0 mm (0.04 in)
2 = White ferrules, 0.5 mm (0.02 in)
* = Stripping only for reinforced cables