Copy set up
Copies the settings of the actual channel to the selected channel (including alarm set
points). The last two characters of the channel identifier of the target channel are
substituted by the channel number.
Integration > Set-up
identical to “Analogue
inputs - integration - ...”.
Set-up only required if the result of the mathematics calculation is to be integrated,
e.g. for quantity calculations.
Limits > Set-up identical
to “Analogue inputs -
limit values - ...”.
Set-up only required if the result of the mathematics calculation is to be monitored for
limit infringements.
Digital inputs (option):
•
Set-up is only required if digital inputs (option, e.g. for counters/events)
are to be used.
Function
Activating the input releases the preset function. The digital inputs are “active high”,
this means that the selected action happens when the control is connected to
+12...+30 V DC. See “Connections/terminal layout”.
5. Set-up unit
79