Other Function
b10
b14
b13
b11
b15
b12
b16
0.50Hz
1.00
15.0kHz
0
0
0
Carrier frequ-
ency setting
STOP key
validity during
terminal operation
Initialization
mode(parameters
or trip history)
Resume on
FRS cancel-
lation mode
Start frequency
adjustment
Frequency scalar
conversion factor
Country code
for initialization
Sets the starting frequency for the inverter
output, range is 0.50 to 10.00Hz in units
of 0.01Hz
Specify a constant to scale the displayed
frequency for [d08] monitor, range is
0.01 to 99.9 in units of 0.01
Sets the PWM carrier frequency, range
is 0.5 to 16.0kHz in units of 0.1kHz.
Select whether the STOP key on the k
eypad is enabled, two option codes:
0.... stop enabled
1.... stop disabled
¡
¡
¡
¡
¡
Select the type of initialization to occur,
two option codes:
0.... Trip history clear
1.... Parameter initialization
Select how the inverter resumes opera-
tion when the free-run stop (FRS) is
cancelled, two options:
0... Restart from 0Hz
1....Restart from frequency detected from
real speed of motor
2.....Free run stop
Select default parameter values for cou-
ntry on initialization, three options,
option codes:
0.... Korea version
1.... Europe version
2.... US version
0
¡
o
b09
0
Software lock
mode selection
¡
Software Lock Mode
Prevents parameter changes, in four
options, option codes:
0.... All parameters except b09 are locked
when SFT from terminal is on
1.... All parameters except b09 and out-
put frequency F01 are locked when
SFT from terminal is ON
2.... All parameters except b09 are locked
3.... All parameters except b09 and output
frequency F01 setting are locked
b17
Communication
number
¡
Sets the communication number for
communication, range is 1 to 32
1
Func-
code
Name
Description
Defaults
Run-
time
Edit
Func-
code
Name
Description
Defaults
9-17
ENDA E-100
INSTRUCTION MANUAL