V
100%
0
(A04)
Base
Frequency
(A03)
Maximum
Frequency
A06
A05
A07
A08 10V
OV
20mA
4mA
Frequency
Analog Input
Expanded Function Mode of A Group
Basic parameter settings
Func-
code
Name
Description
Frequency
commanding
(Multi-speed
commanding
method)
Defaults
A01
A02
A03
A04
Run
commanding
Base frequency
setting
Maximum
frequency
setting
Four options: select codes:
0.... Keypad potentiometer
1.... Control circuit terminal input
2.... Standard operator
3.... Remote operator(communication)
Set the method of run commanding:
0.... Standard operator
1.... Control circuit terminal input
2.... Remote operator(communication)
0
0
60.00Hz
¡
¡
¡
Settable from the base frequency [A03]
up to 400Hz in units of 0.1 Hz.
Settable from 0 to maximum frequency
in units of 0.01Hz
Analog Input Settings
External
frequency
setting start
External
frequency
setting end
A05
A06
End frequency provided when analog
input is 10V(20mA) can be set in units
of 0.01Hz. setting range is 0 to 400Hz
0.00Hz
0.00Hz
¡
¡
Start frequency provided when analog
input is 0V (4mA) can be set in
units of 0.01Hz setting range is 0 to
400 Hz
60.00Hz
¡
Run-
time
Edit
9-7
ENDA E-100
INSTRUCTION MANUAL