A 35
A 37
Running
Free run DC braking
0
+
-
time
The delay from the end of Run command
to start of DC braking (motor free runs
until DC braking begins).
Setting range is 0.0 to 5.0sec in units of
0.1set.
DC Braking Settings
Func-
code
Name
Description
DC braking
time setting
Defaults
Run-
time
Edit
A33
A34
A35
A36
A37
0
0.50Hz
0.0sec
10.0%
¡
¡
¡
¡
Sets two options for DC braking
0.... Disable
1.... Enable
The frequency at which DC braking
occurs, range is 0.0 to 10.0 Hz in units
of 0.01Hz
Applied level of DC braking force,
settable from 0 to 50% in units of 0.1%
Sets the duration for DC braking, range
is 0.0 to 10.0 seconds in units of 0.1sec.
DC braking
frequency
setting
DC braking
output delay
time setting
DC braking
force setting
DC braking
function selection
Frequency-related Functions
A38
A39
A40
A42
A44
0.00Hz
0.00Hz
¡
¡
Sets a limit on output frequency greater
than zero. Range is 0.00 to 400.0Hz in
units of 0.01Hz
Frequency
lower limit
setting
Jump(center)
frequency
setting
Frequency
upper
limit setting
Up to 3 output frequencies can be defined
for the output to jump past to avoid motor
resonances(center frequency) range is
0.00 to 400.0Hz in units of 0.01Hz.
A38
A39
Output frequency
Upper
limit
Settable range
Frequency command
Lower
limit
Sets a limit on output frequency less than
the maximum frequency(A04). Range is
0.00 to 400.0Hz in units of 0.01Hz.
0.0sec
¡
0.00Hz
¡
9-10
ENDA E-100
INSTRUCTION MANUAL