RY
CM2 11
Terminal
symbol
Description
Frequency
arrival
signal
Run signal
Overload
advance
notice signal
PID control error
deviation signal
Alarm signal
Common
terminal
Frequency arrival [FA1][FA2] signals is indicated
when the output frequency accelerates and
decelerates to arrive at a constant frequency.
When the [RUN] signal is selected, the inverter
outputs a signal on that terminal when it is in
the RUN mode.
When the output current exceeds a preset value,
the [OL] terminal signal turns on.
When the PID loop error magnitude the
preset value, the [OD] terminal signal
turns on.
The inverter alarm signal is active when a fault
has occurred.
Common terminal for intelligent output terminal
FA1
(1)
FA2
(2)
RUN
(0)
OL
(3)
OD
(4)
AL
(5)
In
te
ll
ig
en
t
o
ut
pu
t
te
rm
in
al
(1
1)
CM 2
Output terminal
specification
open-collector
output
27V DC max
50
§
max
FA1
FA2
Frequency
F01 set value
Time
ON at
constant
frequency
Frequency
Thresholds
Time
C22
C21
ON at target
frequency
Terminal name
8-3
ENDA E-100
INSTRUCTION MANUAL