When the terminal [JG] is turned on and
the Run command is issued, the inverter
outputs the programmed jog frequency
to the motor.
¡
The frequency for the jogging operation is
set by parameter .
¡
Set the value (terminal mode) in (Run command)
¡
Since jogging does not use an acceleration ramp, we recommend
setting the jogging frequency in to 5Hz or less to prevent tripping.
The type of deceleration used to end a motor jog is selectable by
programming function The options are:
0 : Free-run stop (coasting)
1 : Deceleration (normal level) and stop
2 : DC braking and stop
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
6
JG
Jogging
ON
OFF
Inverter is in Run Mode, output to
motor runs at jog parameter
frequency.
Inverter is in Stop Mode.
Valid for inputs:
Required setting
C01,C02,C03,C04,C05
A02, A26, A27
Notes:
¡
No jogging operation is performed when
the set value of jogging frequency A26 is
smaller than the start frequency B10 or the
value is 0Hz.
¡
Be sure to stop the motor when switching
the function [JG] on or off.
Example:
CM1 5
4
3
2
1
JG FW
8-9
0:Free-run stop
1:Deceleration stop
2:DC braking stop