USP FW
Option
Code
Terminal
Symbol
Function Name
Input
State
10
USP
Unattended Sart
Protection
ON
OFF
On power up, the inverter will not
resume a Run command (mostly
used in the Us)
Valid for inputs:
Required setting
C01,C02,C03,C04,C05
(none)
Notes:
¡
Note that when a USP error occurs and
it is canceled by a reset from a [RS]
terminal input, the inverter restarts
running immediately.
¡
Even when the trip state is canceled by
turning the terminal [RS] on and off after
an under voltage protection E09 occurs,
the USP function will be performed.
¡
When the running command is active
immediately after the power is turned on,
a USP error will occur. When this function
is used, wait for at least three seconds after
the power up to generate a Run command.
Example:
On power up, the inverter will not
resume a Run command that was
active before power loss
Description
8-14
ENDA E-100
INSTRUCTION MANUAL