(L1,L2,U,V,W,P,RB )
Signal input line
(CM1,5,4,3,2,1,H,O/OI,L, FM,CM2,11)
Note2)
Use a twisted and shielded wire for the signal line, and cut the shielded
covering as shown in the diagram below. Make sure that the length of the
signal line is 20 meters or less
Note3)
When the frequency setting signal is turned on and off with a contact, use
a relay which will not cause contact malfunctions, even with the extremely
weak currents and voltages.
Note4)
Use relays which do not have contact defects at 24 V DC, 3mA for the
other terminals.
Note5)
Separate the main circuit wiring from the relay control circuit wiring.
If they must cross, be sure that they cross at a right angle.
Note6
)
Do not short circuit the terminals H-L of the control circuit.
Note7)
Do not short circuit the terminals H-OI of the control circuit.
Insulate
No grounding necessary
Connect to the common terminal[CM1] and [L] of the inverter
Right angle
Separate by 10cm or more
Main circuit power line
6-5