8.3 Intelligent Input Terminal Function
Forward Run/Stop[FW] and Reverse Run/Stop Command[RV]
¡When you input the Run command via the terminal [FW], the inverter executes
the Forward Run command (high) or Stop command(low).
¡When you input the Run command via the terminal [RV], the inverter executes
the Reverse Run command(high) or Stop command(low).
Option
Code
Terminal
Symbol
Function Name State
Description
0
1
FW
RV
Forward Run/
Stop
Reverse Run/
Stop
ON
OFF
ON
OFF
Inverter is in Run Mode, motor
runs forward
Inverter is in Run Mode, motor stop
Inverter is in Run Mode, motor
runs reverse
Inverter is in Run Mode, motor
runs stop
Valid for inputs:
Required setting
C01,C02,C03,C04,C05
A02=01
Notes:
¡
When the Forward Run and Reverse
Run commands are active at the same
time, the inverter enters the Stop Mode.
¡
When a terminal associated with either
[FW] or [RV] function is configured for
normally closed, the motor starts rot-
ation when that terminal is discon-
nected or otherwise has no input
voltage. Set the parameter to
Example:
DANGER :
If the power is turned on and the Run command is already
active, the motor starts rotation and is dangerous! Before turning power on,
confirm that Run command is not active.
CM1 5
4
3
2
1
RV FW
SWR SWF
8-5
ENDA E-100
INSTRUCTION MANUAL