Expanded Function mode of B Group
Restart Mode
b01
b02
b03
0
1.0sec
1.0sec
Allowable
instantaneous
power failure
time setting
Reclosing stand
by after
instantaneous
power failure
recovered
Selection of
restart mode
Select inverter restart method, four option
codes:
0.... Alarm output after trip, no automatic
restart
1.... Restart at 0Hz
2.... Resume operation after frequency
matching
3.... Resume previous freq. after freq.
matching, then decelerate to stop and
display trip info.
¡Restart trip is overcurrent, overvoltage
and under voltage.
¡Overcurrent and over voltage trip restart
up to 3 times, under voltage trip restart
up to 10time.
The amount of time a power input under
voltage can occur without tripping the
power failure alarm. Range is 0.3 to 1.0
sec. If under-voltage exists longer than
this time, the inverter trips, even if the
restart mode is selected.
¡
¡
¡
Time delay after under-voltage condition
goes away, before the inverter runs motor
again. Range is 0.3 to 3.0 seconds.
b02
b03
Input power
Motor speed
failure
Func-
code
Name
Description
Defaults
Run-
time
Edit
Func-
code
Name
Description
9-15
ENDA E-100
INSTRUCTION MANUAL