6.
Change the value in the display to match the reading from the milliameter.
If the calibration was successful, the screen below appears.
If the user entered value is more than ±1 mA different from the nominal value, a
possible error screen appears.
7.
To force the transmitter to accept the calibration, choose
Yes
.
8.
To return to the main display, press MENU and then EXIT.
Calibration
70
Rosemount TCL