Appendix B: Product Certifications
November 2014
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16:
Inspection and maintenance of electrical installation (other than mines).”
GB50257-1996 “Code for construction and acceptance of electric device for
explosion atmospheres and fire hazard electrical equipment installation”
N3
NEPSI Type n
Certificate: GYJ12.1035U
Standards: GB3836.1-2010, GB3836.8-2003
Markings: Ex nA nL IIC T4/T5 Gc
Special Conditions for Safe Use (X):
1.
This component is not capable of withstanding the 500V electrical strength test
defined in Clause 8.1 of GB3836.8-2003. The must be taken into account during
installation.
2.
This component must be housed in a suitable component certified enclosure
that provides a degree of protection of at least IP54 and meets the relevant
material and environmental requirements of GB3836.1-2010 and
GB3836.8-2003.
3.
Provision must be made, external to the component, to ensure the rated voltage
of the component supply is not exceeded by transient disturbances of more the
40%.
4.
The ambient temperature range is:
5.
Maximum input voltage: 42.4V.
6.
End users are not permitted to change any components inside, but to settle the
problem in conjunction with manufacturer to avoid damage to the product.
7.
During installation, use and maintenance of this product, observe following
standards:
GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13:
Repair and overhaul for apparatus used in explosive gas atmospheres”
GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15:
Electrical installations in hazardous area (other than mines)”
GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16:
Inspection and maintenance of electrical installation (other than mines)”
GB50257-1996 “Code for construction and acceptance of electric device for
explosion atmospheres and fire hazard electrical equipment installation
engineering”
B.5.3
Japan
I4
TIIS FISCO Intrinsic Safety (ia)
Certificate: TC19713
Markings: IIC T4
H4
TIIS FISCO Intrinsic Safety (ib)
Certificate: TC20737
Markings: IIC T4
T code
Ambient Temperature
T4
-50
°C
≤
Ta
≤
+85
°C
T5
-50 °C
≤
Ta
≤
+70 °C
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......