Appendix B
Product Certificates
European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 69
Intrinsically Safe and Non-Incendive installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 81
Installation drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 82
B.1
European Directive Information
A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The
most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com.
B.2
Ordinary Location Certification from FM
Approvals
As standard, the transmitter has been examined and tested to determine that the design meets
the basic electrical, mechanical, and fire protection requirements by FM Approvals, a nationally
recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health
Administration (OSHA).
B.3
Installing Equipment in North America
The US National Electrical Code (NEC) and the Canadian Electrical Code (CEC) permit the use of
Division marked equipment in Zones and Zone marked equipment in Divisions. The markings
must be suitable for the area classification, gas, and temperature class. This information is
clearly defined in the respective codes.
B.3.1
USA
I5
FM Intrinsically Safe and Nonincendive
Certificate: 3011568
Standards: FM Class 3600:1998, FM Class 3610:2010, FM Class 3611:2004, FM Class
3810:2005, ANSI/ISA 60079-0:2009, ANSI/ISA 60079-11:2009, NEMA
250:1991, IEC 60529:2011
Markings: IS CL I, DIV 1, GP A, B, C, D; T4 (-50 °C
≤
Ta
≤
+60 °C); NI CL I, DIV 2, GP A, B, C, D;
T4A (-50 °C
≤
Ta
≤
+85 °C); T5 (-50 °C
≤
Ta
≤
+70 °C) when installed per
Rosemount drawing 00848-4404
Note
Transmitters marked with Nonincendive CL I, DV 2 can be installed in Division 2 locations using
general Division 2 wiring methods or Nonincendive Field Wiring (NIFW). See Drawing
00848-4404.
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......