32
Reference Manual
00809-0100-4697, Rev GA
Section 3: Configuration
November 2014
Configuration
3.4.3
PlantWeb alerts
The alerts and recommended actions should be used in conjunction with
.
The Resource Block will act as a coordinator for PlantWeb alerts. There will be three alarm
parameters (FAILED_ALARM, MAINT_ALARM, and ADVISE_ALARM) which will contain
information regarding some of the device errors which are detected by the transmitter
software. There will be a RECOMMENDED_ACTION parameter which will be used to display the
recommended action text for the highest priority alarm and a HEALTH_INDEX parameters (0 -
100) indicating the overall health of the transmitter. FAILED_ALARM will have the highest
priority followed by MAINT_ALARM and ADVISE_ALARM will be the lowest priority.
FAILED_ALARMS
A failure alarm indicates a failure within a device that will make the device or some part of the
device non-operational. This implies that the device is in need of repair and must be fixed
immediately. There are five parameters associated with FAILED_ALARMS specifically, they are
described below.
FAILED_ENABLED
This parameter contains a list of failures in the device which makes the device
non-operational that will cause an alert to be sent. Below is a list of the failures with the
highest priority first.
Table 3-5. Failure Alarms
FAILED_MASK
This parameter will mask any of the failed conditions listed in FAILED_ENABLED. A bit on
means that the condition is masked out from alarming and will not be reported.
Alarm
Priority
ASIC Failure
1
Electronics Failure
2
Hardware/Software Incompatible
3
Memory Failure
4
Body Temperature Failure
5
Sensor 1 Failure
6
Sensor 2 Failure
7
Sensor 3 Failure
8
Sensor 4 Failure
9
Sensor 5 Failure
10
Sensor 6 Failure
11
Sensor 7 Failure
12
Sensor 8 Failure
13
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......