Table 3-21. Transducer Status Sub-parameter Structure
Table 3-22. DUAL_SENSOR CONFIG Sub-parameter Structure
Table 3-23. DUAL_SENSOR_STATUS Sub-parameter Structure
Transducer status table
0x01
A/D Failure
0x02
Sensor Failure
0x04
Dual Sensor Failure
0x08
CJC Degraded
0x10
CJC Failure
0x20
Body Temp Failure
0x40
Sensor Degraded
0x80
Body Temperature Degraded
Parameter
Description
DUAL_SENSOR_MODE
Disables or enables a sensor for configuration
DUAL_SENSOR_TAG
Differential description
INPUT_A
Sensor to be used in DUAL_SENSOR_CALC
INPUT_B
Sensor to be used in DUAL_SENSOR_CALC
DUAL_SENSOR_CALC
Equation used for the dual sensor measurement including: Not Used,
Difference (Input A - Input B), and Absolute Difference (Input A - Input B)
ENG_UNITS
Units used to display sensor parameter
UPPER_RANGE
Upper Differential Limit (Input A High - Input B Low)
LOWER_RANGE
Lower Differential Limit (Input A Low - Input B High)
Dual sensor status table
0x00
Active
0x01
Out of Service
0x02
Inactive
0x04
Component Sensor Open
0x08
Component Sensor Short
0x10
Component Sensor Out of Range or Degraded
0x20
Component Sensor Out of Limits
0x40
Component Sensor Inactive
0x80
Configuration Error
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......