Appendix D: Function Blocks
November 2014
Function Blocks
05
MODE_BLK
None
The actual, target, permitted, and normal modes of
the block.
Actual: The mode the “block is currently in”
Target: The mode to “go to”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
06
BLOCK_ERR
None
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.
07
PV
EU of
XD_SCALE
The process variable used in block execution.
08
OUT
EU of
OUT_SCALE
or XD_SCALE
if in direct
L_TYPE
The block output value and status.
09
SIMULATE
None
A group of data that contains the current transducer
value and status, the simulated transducer value and
status, and the enable/disable bit.
10
XD_SCALE
None
The high and low scale values, engineering units code,
and number of digits to the right of the decimal point
associated with the channel input value. The
XD_SCALE units code must match the units code of
the measurement channel in the transducer block. If
the units do not match, the block will not transition to
MAN or AUTO.
11
OUT_SCALE
None
The high and low scale values, engineering units code,
and number of digits to the right of the decimal point
associated with OUT when L_TYPE is not direct.
12
GRANT_DENY
None
Options for controlling access of host computers and
local control panels to operating, tuning, and alarm
parameters of the block. Not used by device.
13
IO_OPTS
None
Allows the selection of input/output options used to
alter the PV. Low cutoff enabled is the only selectable
option.
14
STATUS_OPTS
None
Allows the user to select options for status handling
and processing. The options supported in the AI block
are the following:
Propagate fault forward
Uncertain if limited
Bad if limited
Uncertain if Manual mode.
15
CHANNEL
None
The CHANNEL value is used to select the
measurement value. Configure the CHANNEL
parameter before configuring the XD_SCALE
.
16
L_TYPE
None
Linearization type. Determines whether the field
value is used directly (Direct), is converted linearly
(Indirect), or is converted with the square root
(Indirect Square Root).
17
LOW_CUT
%
If percentage value of transducer input fails below
this, PV = 0.
Table D-1. Analog Input Function Block Parameters
Number
Parameter
Units
Description
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......