Section 3: Configuration
November 2014
Configuration
3.2.8
Configure measurement validation
Use the following steps to configure measurement validation:
1.
Set mode to Disabled for specific sensor.
2.
Select sample rate. 1-10 sec/sample is available. 1 second/sample is preferred for
sensor degradation. The higher the number of seconds between samples, the more
emphasis put on process variation.
3.
Select Deviation Limit from 0 to 10 units. If deviation limit is exceeded, a status event
will be triggered.
4.
Select Increasing Limit. Sets the limit for increasing rate of change. If limit is exceeded, a
status event will be triggered.
5.
Select Decreasing Limit. Sets the limit for decreasing rate of change. If limit is exceeded,
a status event will be triggered.
Note
The decreasing limit selected is required to be a negative value.
6.
Set the Deadband from 0 to 90%. This threshold is used to clear the PV status.
7.
Set Status Priority. This determines what happens when the specific limit has been
exceeded. No Alert - Ignores limit settings. Advisory - Sets Advisory Plant Web Alert,
but does not do anything with PV status. Warning - Sets a Maintenance Plant Web Alert
and sets PV status to uncertain. Failure - Sets A Failure Plant Web Alert and sets PV
status to Bad.
8.
Set mode to Enabled for specific sensor.
3.3
Common configurations for high density
applications
For the application to work properly, configure the links between the function blocks and
schedule the order of their execution. The Graphical User Interface (GUI) provided by the
F
OUNDATION
fieldbus host or configuration tool will allow easy configuration.
The measurement strategies shown in this section represent some of the common types of
configurations available in the 848T. Although the appearance of the GUI screens will vary from
host to host, the configuration logic is the same.
Note
Ensure the host system or configuration tool is properly configured before downloading the
transmitter configuration. If configured improperly, the F
OUNDATION
fieldbus host or
configuration tool could overwrite the default transmitter configuration.
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......