Section 3: Configuration
November 2014
Configuration
3.4.4
Recommended actions for PlantWeb alerts
RECOMMENDED_ACTION
The RECOMMENDED_ACTION parameter displays a text string that will give a recommended
course of action to take based on which type and which specific event of the PlantWeb alerts are
active.
Table 3-7. RB.RECOMMENDED_ACTION
Alarm type
Active event
Recommended action
None
None
No action required
Advisory
Excessive Deviation
Verify the process temperature, sensor wiring, and check
sensor integrity.
Advisory
Excessive Rate of
Change
Verify sensor wiring is appropriate in each junction point and
check sensor integrity.
Maintenance
CJC Degraded
If T/C sensors are being used, restart the device. If condition
persists, replace the device.
Maintenance
Body Temperature
Out of Range
Verify the ambient temperature is within operating limits.
Maintenance
Sensor 1 Degraded
Confirm the operating range of Sensor 1 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 2 Degraded
Confirm the operating range of Sensor 2 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 3 Degraded
Confirm the operating range of Sensor 3 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 4 Degraded
Confirm the operating range of Sensor 4 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 5 Degraded
Confirm the operating range of Sensor 5 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 6 Degraded
Confirm the operating range of Sensor 6 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 7 Degraded
Conform the operating range of Sensor 7 and/or verify the
sensor connection and device environment.
Maintenance
Sensor 8 Degraded
Confirm the operating range of Sensor 8 and/or verify the
sensor connection and device environment.
Failed
Sensor 1 Failure
Verify the Sensor 1 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 2 Failure
Verify the Sensor 2 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 3 Failure
Verify the Sensor 3 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 4 Failure
Verify the Sensor 4 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 5 Failure
Verify the Sensor 5 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 6 Failure
Verify the Sensor 6 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Failed
Sensor 7 Failure
Verify the Sensor 7 Instrument process is within the Sensor
range and/or confirm sensor configuration and wiring.
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......