48
Reference Manual
00809-0100-4697, Rev GA
Section 3: Configuration
November 2014
Configuration
Table 3-18. SENSOR_STATUS Sub-parameter Structure
Table 3-19. SENSOR_CAL Sub-parameter Structure
Table 3-20. CAL_STATUS Structure
Sensor status table
0x00
Active
0x01
Out of Service
0x02
Inactive
0x04
Open
0x08
Short
0x10
Out of Range
0x20
Beyond Limits
0x40
Excess EMF Detected
0x80
Other
Parameter
Description
SENSOR_NUMBER
The sensor number to calibrate
CALIB_POINT_HI
The High calibration point for the selected sensor
CALIB_POINT_LO
The Low calibration point for the selected sensor
CALIB_UNIT
The engineering units used for calibrating the sensor
CALIB_METHOD
The method of the last calibration for sensor
103 - factory trim standard calibration
104 - user trim standard calibration
CALIB_INFO
Information regarding the calibration
CALIB_DATE
Date that the calibration was completed
CALIB_MIN_SPAN
The minimum calibration span value allowed. This minimum span
information is necessary to ensure that when calibration is done, the two
calibrated points are not too close together
CALIB_PT_HI_LIMIT
The High calibration unit
CALIB_PT_LO_LIMIT
The Low calibration unit
Cal status
0
No Command Active
1
Command Executing
2
Command Done
3
Command Done: Errors
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......