Appendix D: Function Blocks
November 2014
Function Blocks
Block errors
lists conditions reported in the BLOCK_ERR parameter. Conditions in bold are inactive
for the ISEL block and are given for reference.
Table D-7. BLOCK_ERR Conditions
Modes
The ISEL function block supports three modes of operation as defined by the MODE_BLK
parameter:
Manual (Man)
The block output (OUT) may be set manually.
Automatic (Auto)
OUT reflects the selected value.
Out of Service (OOS)
The block is not processed. The BLOCK_ERR parameter shows Out of Service. The target
mode of a block may be restricted to one or more of the supported modes. In this mode,
changes can be made to all configurable parameters.
Number
Name and description
0
Other: The output has a quality of uncertain.
1
Block Configuration Error: Select type is not configured
2
Link Configuration Error
3
Simulate Active
4
Local Override
5
Device Fault State Set
6
Device Needs Maintenance Soon
7
Input Failure/Process Variable has Bad Status: One of the inputs is Bad.
8
Output Failure
9
Memory Failure
10
Lost Static Data
11
Lost NV Data
12
Readback Check Failed
13
Device Needs Maintenance Now
14
Power Up: The device was just powered-up.
15
Out of Service: The actual mode is out of service.
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......