17
Reference Manual
00809-0100-4697, Rev GA
Section 2: Installation
November 2014
Installation
2.7.2
Using conduit entries
Use the following steps to install the 848T with conduit entries.
1.
Remove the junction box cover by unscrewing the four cover screws.
2.
Remove the five conduit plugs and install five conduit fittings (supplied by the installer).
3.
Run pairs of sensor wires through each conduit fitting.
4.
Install the sensor wires into the correct screw terminals (follow the label on the
electronics module).
5.
Install the power/signal wires into the correct screw terminals. Power is polarity
insensitive, allowing the user to connect positive (+) or negative (–) to either fieldbus
wiring terminal labeled “Bus.”
6.
Replace the junction box cover and securely tighten all cover screws.
Figure 2-12. Installing the 848T with Conduit Entries
A. Enclosure cover screw
B. Sensors 1 and 2 conduit
C. Sensors 3 and 4 conduit
D. Sensors 5 and 6 conduit
E. Sensors 7 and 8 conduit
F. Power/signal
A
B
C
D
E
F
Summary of Contents for Rosemount 848T
Page 2: ......
Page 4: ...ii Reference Manual 00809 0100 4697 Rev GA Title Page November 2014 ...
Page 12: ...4 Reference Manual 00809 0100 4697 Rev GA Section 1 Introduction November 2014 Introduction ...
Page 26: ...18 Reference Manual 00809 0100 4697 Rev GA Section 2 Installation November 2014 Installation ...
Page 134: ...Index 4 Reference Manual 00809 0100 4697 Rev GA Index November 2014 Index ...
Page 135: ......