Optional modules parameters
Table 3-6:
Description
Common features
Port B/Port C (Op-
tional module)
•
RS-232 - P/N:
1-360-024
•
RS-485 Half
Duplex - P/N
1-360-03-023
•
Expansion I/O
Module - P/N
1-360-03-026
(232/485 Half
Duplex, Ether-
net switch)
Note
Port C is only
available with
Retrofit Enclo-
sure.
•
Typically used for general commu-
nications with a flow computer,
RTU (Modbus slave) and radios.
•
RS-485 -- 2-wire (Half Duplex) con-
nected to TX+ and TX- (P/N
1-360-03-026) or A and B (P/N
1-360-03-023)
•
Factory default is RS-232, Ad-
dress32, 19200baud
•
Communications via Daniel Me-
terLink using RS-232
•
Software configurable Modbus
Address (1-247)
•
Auto-detects TCP/IP and ASCII or
RTU Protocol
-
ASCII Protocol:
-
Start Bits = 1, Data Bits =
7
-
Parity: odd or even 1, Stop Bits
= 1
-
Baud Rates: 1200, 2400, 9600,
19200, 38400, 57600, 115000
bps
-
RTU Protocol:
-
Start Bits = 1, Data Bits =
8
-
Parity: odd or even 1, Stop Bits
= 1
-
Baud Rates: 1200, 2400, 9600,
19200, 38400, 57600, 115000
bps
(1) Denotes auto-detected protocols
Note
Use of FODO6 requires DI1Mode set to Frequency/Digital Output 6. Digital Input will not be
available.
Electrical installation
Installation manual
71
Summary of Contents for Daniel 3410 Series
Page 8: ......
Page 122: ...Engineering drawings 112 Gas Ultrasonic Flow Meter ...
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 139: ...Open source licenses Installation manual 125 ...