Installation, Operation and Maintenance Manual
MAN-02-04-97-0713-EN Rev. 1
October 2019
23
Installation
Section 3: Installation
Important points to note:
•
Do not damage the explosion-proof mating surfaces on the housing and on the
electrical covers.
•
Reinstall all the screws associated with the dismantled parts, and coat them with
a thread sealant after coating them with a film of copper- or molybdenum-based
grease. This will prevent the screws from sticking and facilitate their removal when
maintenance is required.
•
Check that the bolts and screws are of the same dimensions and at least equal
quality to those originally installed (as stated on the nameplate).
DANGER
Do not electrically operate the actuator when the electrical covers are removed. Do not
open the actuator covers when an explosive atmosphere may be present. Ignoring the
above precautions may result in personal injury or death.
•
Replace any weather-proof seals that may have been removed (O-ring for the
covers, O-ring for the explosion-proof joint of the motor).
3.10
Installation in Environments with
Explosive Dusts
NOTICE
The Bettis XTE3000 electric actuator shall be installed and maintained according to the
applicable rules regarding electrical installation in hazardous areas (other than mines), classified
as zone 21 (dust); for example: EN 50281-1-2 (dust) and/or other national standards.
Ensure that:
•
The joint surfaces are greased with silicone oil or equivalent before assembly.
•
The cable glands have minimum protection degree IP6X (EN 60529).